Daikin VRV S RXQ4/5ARV1 Service Manual page 59

Table of Contents

Advertisement

SiAF332111E
Maintenance
Menu
Addressed
Sensor
Value
1: Displays suction air temperature after correction for all models.
2: Displays temperature only for applicable models.
3: Displays floor temperature used for control (including correction) when the sensor kit is
connected.
4: Displays control temperature (temperature near the person when the sensor kit is
connected).
5: Displays suction air temperature after correction when the sensor kit is connected.
6: Areas mean four areas shown on the below.
7: For human presence detection rate (%), human motion is recognized by digital output
ranging from 0 to 5 V. (5 V is output when no human presence is detected, and 0 V is output
when human presence is detected.)
Reference
(1) 0% detection rate: Human presence is not detected at all.
(2) 25% detection rate: Human presence is detected, but the sensor does not recognize human
presence.
(3) 50% detection rate: The sensor recognizes human presence (small human motion).
(4) 75% detection rate: The sensor recognized human presence (large human motion).
(5) 100% detection rate: The sensor constantly outputs 0 V. Continuing this condition will
display an error.
8: Directly displays a measured value sent from the adaptor PCB.
Part 3 Remote Controller
Item 2
Unit No.: 0 - 15
Code
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
22:
23:
24:
25:
26:
Data
4
1
3
2
80 cm above the floor
Service Settings Menu, Maintenance Menu
Remarks
Select the unit number you want to check.
Remote controller thermistor (°C)
Suction air thermistor (°C) 5
Heat exchanger liquid pipe thermistor (°C)
Heat exchanger gas pipe thermistor (°C)
Indoor unit address No.
Outdoor unit address No.
BS unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
Displays human presence detection rate (%) (see 7) in
Area 1 (see 6). Display value × 10%. Displays 15 for
units with no sensing type mounted.
Displays human presence detection rate (%) (see 7) in
Area 2 (see 6). Display value × 10%. Displays 15 for
units with no sensing type mounted.
Displays human presence detection rate (%) (see 7) in
Area 3 (see 6). Display value × 10%. Displays 15 for
units with no sensing type mounted.
Displays human presence detection rate (%) (see 7) in
Area 4 (see 6). Display value × 10%. Displays 15 for
units with no sensing type mounted.
Infrared sensor (°C) (See 8). Displays – for units with
no sensing type mounted.
The corresponding data will be displayed, based on the
Unit No. and Code selected.
Detection areas of presence sensor
(Corresponding to the punched mark
on the inner frame of the panel:
†~††††)
53