Troubleshooting by Error Code
5.24 Missing of Leakage Detection Core
Applicable
RXMQ8-12AR
Models
E2
Error Code
Sub code: 06
Method of Error
Detect error according to whether or not there is continuity across the connector (X101A).
Detection
Error Decision
When no current flows at the time of turning ON the power supply.
Conditions
Supposed
Disconnection of connector (X101A)
Causes
Wiring disconnection
Defective outdoor unit main PCB
Troubleshooting
232
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn OFF the power supply,
and then disconnect
compressor leads.
Is the system reset to
normal?
NO
Is X101A connected?
YES
YES
NO
SiAF332111E
The error is considered to have
resulted from external factors
other than failures (e.g. noise).
Properly connect the connector.
Replace the outdoor unit main
PCB (A1P).
Part 6 Service Diagnosis