Field Settings for Outdoor Unit (6/8 HP Models)
RXMQ8AR
(3) BS button (BS1~BS3)
(1) Microcomputer normal monitor
This monitor blinks while in normal control, and turns ON or OFF when an error occurs.
(2) 7 segment display
 Used to check the transmission.
 Used to display the transmission state between indoor and outdoor units.
 Used to display the contents of error.
 Used to display the contents of field setting.
(3) BS button
Used to change mode.
(4) DIP switch
Used to make field settings.
The figure below shows the required position of the DIP switches on spare PCB. Change DIP
switches at time of power disconnected.
Application model
RXMQ6ARV1
RXMQ8ARY1
124
(2) Segment display (SEG1~SEG3)
Connection terminal
for transmission use
The setting method (represents the position of switches)
ON
OFF
1 2 3 4
1 2 3 4
DS2
DS1
ON
OFF
1 2 3 4
1 2 3 4
DS1
DS2
(4)
DIP switch
(DS1-1~4)
(DS2-1~4)
Initial position of DIP switches („)
ON
OFF
1 2 3 4
DS1
(1)
Microcomputer
normal monitor
(HAP)
Set DS1-2, DS1-3, DS1-4, DS2-1, and DS2-3 to
ON.
Set DS1-2, DS1-3, DS1-4, DS2-1, DS2-2, and
DS2-3 to ON
Part 5 Field Settings and Test Operation
SiAF332111E
1 2 3 4
DS2