Environmental Limits; Electrical Data And Options - ABB 265GS Operating Instruction

Pressure transmitter
Table of Contents

Advertisement

Specifications
9.4

Environmental limits

Change from one to two columns
Electromagnetic compatibility (EMC)
Conforms to the requirements and tests for EMC Directive 89/336/EC,
as well as to EN 61000-6-3 concerning emitted interference and
EN 61000-6-2 concerning interference immunity.
Meets NAMUR recommendations.
Low Voltage Directive
Complies with 73/23/EC.
Pressure Equipment Directive (PED)
Complies with 97/23/EC Category III, module H.
Humidity
Relative humidity:
Condensation, icing:
Change from one to two columns
9.5

Electrical data and options

Change from one to two columns
aaaaaad
HART digital communication and 4 ... 20 mA output current
Power supply
The transmitter operates from 10.5 ... 45 V DC with no load and is
protected against reverse polarity connection (additional load allows
operations over 45 V DC).
With a backlit LCD display, the minimum voltage is 14 V DC.
For Ex ia and other intrinsically safe approved versions, the supply
voltage must not exceed 30 V DC.
Ripple
Maximum permissible supply voltage ripple during communication:
Complies with HART FSK "Physical Layer" specification rev. 8.1.
Load limitations
Total loop resistance at 4 ... 20 mA and HART:
Voltage
sup
ply
Minimum
R
k (
) Ω
IMPORTANT (NOTE)
A minimum of 250 Ω resistance is required for HART
communication.
LCD display (optional)
19-segment alphanumeric display (two lines, six characters) with
additional bar chart display; option of backlighting for customized
display of:
Output current in percent
Output current in mA
Freely selectable process variable
Diagnostic messages, alarms, measuring range upper limit violations,
and changes to the configuration are also displayed.
Change from one to two columns
72
Up to 100 %
Permissible
operating
voltage
(
VDC
)
22
5 ,
mA
Vibration resistance
Acceleration up to 2 g at frequencies up to 1,000 Hz (according to
IEC 60068-2-6).
Shock resistance (acc. to IEC 60068-2-27)
Acceleration:
Duration:
Protection type (humid and dusty atmospheres)
The transmitter is dust and sand-tight, and is protected against
immersion effects as defined by the following standards:
IEC EN 60529 (1989) with IP 67 (with IP 68 on request)
NEMA 4X
JIS C0920
Protection type with plug connection: IP 65
Output signal
4 ... 20 mA two-wire output, can be selected by user, linear or freely
programmable with 20 reference points.
HART® communication provides digital process variables (%, mA or
engineering units) superimposed on the 4 ... 20 mA signal (protocol
according to Bell 202 FSK standard).
Output current limits (according to NAMUR standard)
Overload condition:
 Lower limit: 3.8 mA (configurable up to 3.5 mA)
 Upper limit: 20.5 mA (configurable up to 22.5 mA)
Alarm current
Minimum alarm current:
Maximum alarm current:
Default setting:
SIL: Functional safety (optional)
According to IEC 61 508/61 511
Device with certificate of conformity for use in safety-related
applications, up to and including SIL 2.
265Gx, 265Ax
50 g
11 ms
Can be configured from
3.5 ... 4 mA,
Default setting: 3.6 mA
Can be configured from
20 ... 22.5 mA;
Default setting: 21 mA
Maximum alarm current
IM/265Gx/Ax-EN-07