Configuring the parameters
1. Apply the pressure for the "Lower Range Value" and wait approx. 30 s until it has stabilized.
2. Press the 0% button. This sets the output current to 4 mA.
3. Apply the pressure for the "Upper Range Value" and wait approx. 30 s until it has stabilized.
4. Press the 100% button. This sets the output current to 20 mA.
5. If required, reset the damping to its original value.
6. Record the new settings. The respective parameter will be stored in the non-volatile memory
10 s after the 0% or 100% button is last pressed.
NOTICE
Operating the control buttons with a magnetic screwdriver is not permitted.
IMPORTANT (NOTE)
This configuration procedure only changes the 4 ... 20 mA current signal; it does not affect the
physical process pressure shown on the digital display or user interface. To avoid potential
discrepancies, you can make corrections by following the menu path "Calibrate_Pressure
Measurement_Adjust input" in the user interface.
After performing a correction, you must check the device configuration.
IM/265Gx/Ax-EN-07
265Gx, 265Ax
Configuration