PROFIBUS PA output
Model
Pressure transmitter conforming to Profile 3.0, Class A and B;
ID number 04C2 HEX
Power supply
The transmitter is operated at 10.2 ... 32 V DC (no polarity).
The supply voltage must not exceed 17.5 V DC when used in Ex ia
zones.
Intrinsically safe installation in accordance with FISCO model.
Current consumption
Operating (quiescent):
Fault current limit value:
Output signal
Physical layer in accordance with IEC 1158-2/EN 61158-2;
transmission using Manchester II modulation at 31.25 kbit/sec.
Output interface
PROFIBUS PA communication according to Profibus DP50170 Part
2/DIN 19245 Part 1-3
Output cycle time
40 ms
Function blocks
1 standard analog input function block
1 transducer block
1 physical block
LCD display (optional)
19-segment alphanumeric display (two lines, six characters) with
additional bar chart display; option of backlighting.
Customized display:
Output value in percent or OUT (analog input)
Diagnostic messages, alarms, measuring range upper limit violations,
and changes to the configuration are also displayed.
Transmitter interference mode
Permanent self-diagnosis; potential errors indicated in diagnostic
parameters and in the status of process values.
Change from one to two columns
IM/265Gx/Ax-EN-07
11.7 mA
Maximum 17.3 mA
FOUNDATION Fieldbus output
Power supply
The transmitter is operated at 10.2 ... 32 V DC (no polarity).
The supply voltage must not exceed 17.5 V DC when used in Ex ia
zones.
Intrinsically safe installation in accordance with FISCO model.
Current consumption
Operating (quiescent):
Fault current limit value:
Output signal
Physical layer in accordance with IEC 1158-2/EN 61158-2;
transmission using Manchester II modulation at 31.25 kbit/sec.
Function blocks/execution time
1 standard analog input function block/maximum 25 ms,
1 standard PID function block
Additional blocks
1 manufacturer-specific pressure with calibration transducer block
1 enhanced resource block
Number of link objects
10
Number of VCRs
16
Output interface
FOUNDATION Fieldbus digital communication protocol in accordance
with standard H1; complies with specification V. 1.5.
FF registration no.: IT023600
LCD display (optional)
19-segment alphanumeric display (two lines, six characters) with
additional bar chart display; option of backlighting.
Customized display:
Output value in percent or OUT (analog input)
Diagnostic messages, alarms, measuring range upper limit violations,
and changes to the configuration are also displayed.
Transmitter interference mode
Permanent self-diagnosis; potential errors indicated in diagnostic
parameters and in the status of process values.
265Gx, 265Ax
Specifications
11.7 mA
Maximum 17.3 mA