11. TROUBLESHOOTING

11.5 If Communication Error Occurs between Master Station and This Module

"ERR." LED of master station flickers
Parameter
setting match system
configuration?
Y
Any of master
station link special registers
SW0080 to SW0083 (other
station data link status)
ON?
Y
Any of master
station link special registers
SW0098 to SW009B (repeated
station number status)
ON?
Y
Check the module corresponding
to the bit switched on.
Station number switch
setting correct?
Y
Corresponding module faulty
Downloaded from
ManualsNet.com
If any repeated station number bit in any of the link special registers SW0098 to
SW009B (repeated station number status) switches on, check the high-speed counter
module of the corresponding station number in the following flowchart.
Troubleshooting flowchart used when the "ERR." LED of the master station flickers
N
Correct parameter setting
or system configuration.
N
Master station faulty
N
N
Correct station number switch setting.
Switch power on again
or turn on reset switch.
To next page
search engine
Check the module corresponding
to the bit switched on.
N
Power on?
Switch power on.
Y
N
"POWER" LED lit?
Y
Is supply voltage
within specified range?
Corresponding module faulty
N
"RD" LED lit?
Y
Communication cable
wired correctly*1?
Corresponding module faulty
To next page
11 - 4
MELSEC-A
Master side check
High-speed counter module side check
N
Set supply voltage to
Y
within specified range.
N
Correct communication cable wiring.
Y
To next page