11. TROUBLESHOOTING

11. TROUBLESHOOTING

11.1 Count Value Is Incorrect

Is the pulse input mode consistent with the pulse
input setting in the remote register?
Is the sequence program data processed in 24-bit
binary?
Is the terminal for pulse input wired using a
shielded twisted pair cable?
Does noise enter through the ground of the high-
speed counter module?
Have adequate measures been taken against
noise in the panel or noise resulting from the other
equipment?
Is sufficient distance provided between heavy
current equipment and counter input line?
Is the count value the same at CH1 and CH2 after
the same count value was entered?
Does the input pulse waveform match the
performance specifications?

11.2 Count Operation Is Not Performed

Is the external wiring of phases A and
correct?
When a voltage is applied directly to the pulse
input terminals of phases
LEDs of phases
Is the count enable command {RY(n+1)4
(RY(n+1)B} on?
Does the master module indicate an error?
Is the counter function selection start command
{RY(n+1)6 (RY(n+1)D)} on or a voltage applied to
the F.START terminal?
Downloaded from
ManualsNet.com
The following table lists check items for use when the count value is incorrect.
Check Item
The following table lists check items for use when count operation is not performed.
Check Item
A and
B, are the
A and
B lit?
search engine
Make the pulse input mode consistent with the pulse input
setting in the remote register.
Correct the sequence program so that the data is processed
in 24-bit binary.
Use a shielded twisted pair cable for to wire a terminal for
pulse input.
• Disconnect the high-speed counter module from the ground.
• If the high-speed counter module is in contact with the
ground, separate it from the ground.
Provide CR surge suppression to magnetic switches, etc.
Wire the pulse input line independently, and separate in-
panel wiring 150mm (5.91 inch) or more from power line.
If the count values are different, the hardware is faulty.
Please consult your local Mitsubishi representative.
Monitor and confirm the pulse waveform using a
synchroscope. If the waveform does not match the
specifications, enter pulses of a correct waveform.
B
Check the external wiring and make correction.
• If they are lit, check the external wiring and pulse generator
and make correction.
• If they are not lit, the hardware is faulty. Please consult your
local Mitsubishi representative.
Switch on the count enable command {RY(n+1)4 (RY(n+1)B}
using the sequence program.
If the master module is in error, refer to the troubleshooting
procedure of the manual of the master module used and
make operation normal.
When the count disable function has been set by the counter
function selection, switch off {RY(n+1)6 (RY(n+1)D)} or
F.START terminal.
11 - 1
MELSEC-A
Corrective Action
Corrective Action