Mitsubishi Electric AJ65BT-D62 User Manual page 23

High-speed counter module
Hide thumbs Also See for AJ65BT-D62:
Table of Contents

Advertisement

3. SPECIFICATIONS
Counting Speed
Setting Switch
Rise/fall time
t=2µs or less
t=25µs or less
t=500µs
Downloaded from
ManualsNet.com
*Counting speed is influenced by pulse rise time and fall time. Countable speeds
are as follows.
Note that counting of a pulse having long rise and fall times may result in
miscounting.
HIGH
1-phase
2-phase
input
input
200kPPS
200kPPS
10kPPS
10kPPS
——
——
search engine
LOW
1-phase
2-phase
input
input
10kPPS
7kPPS
1kPPS
700PPS
500PPS
250PPS
3 - 3
MELSEC-A
t
t