The warning "Warning! Parallel Firmware Error" will appear in current event
when the parallel setting is enabled, but the firmware does not support this
feature.
The way to release this warning is to turn off the AC power source and shut
down the system. After the system shutdown completely, turn on the AC
power to restart the UPS.
Table 4-10: Setup-Pre-Alarm setting list
Setting Item
Sub Item
Line Voltage
--
Range
Line
Frequency
--
Range
Load
--
Table 4-11: Setup-Parallel setting list
Setting Item
Sub Item
UPS Parallel
--
Independent
--
Battery
4.2.7 Information Screen
In INFORMATION menu, you can check the serial number, firmware versions, system
configuration and settings of the UPS. The INFORMATION has the submenus, Identification,
System and Battery, as shown in Figure 4-28, 4-29.
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 03 17 AA 59 201 24
Explanation
Set line voltage range:
Upper limit
+5%
+10%
+15%
+20% (Default)
Lower limit
-5%
-10%
-15%
-20% (Default)
Set line frequency range:
Upper / Lower limit
+/- 1Hz
+/- 2Hz
+/- 3Hz
+/- 4Hz (Default)
Set UPS Overload percentage (40~100%)
100% (Default)
Set UPS load unbalance percentage (20~100%)
100% (Default)
Explanation
Set UPS parallel
Disable (Default)
Enable
Set Independent Battery
Disable (Default)
Enable