These settings include:
[1] COM Port : The COM port of IR-712A. (RS-232/RS-485, default: RS-232) (*)
[2] Baud Rate : The baud rate of the COM port (9600~115200 bps,default: 115200)
[3] Parity : Parity bit
[4] Data Bits : Data bit (This value is fixed in 8)
[5] Stop Bits : Stop bit (1 / 2, default:1)
[6] Net ID : Modbus Network ID (1~247, default: 1)
[7] GapTime : The max space time in an IR protocol (Fig. 3-5). For example, GapTime
should be set to the value greater than 40 ms to learn IR commands successfully for
the Sharp remote control.
[8] MB Cmd Resp Delay Time: The delay time before the IR-712A responses each
request from the Modbus master devices (Modbus command response delay time: 0
~ 60 ms; default: 3 ms)
* Note: Please refer to the section 2-4.
IR-712A User Manual
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved
1
2
3
7
8
 Figure 3-4 The basic settings window for IR-712A.
(NONE / ODD / EVEN,default:NONE)
 Figure 3-5 A complete IR Command with a large Gap Time.
4
5
6
(6 ~ 200 ms, default:80 ms)
Version 1.9
E-mail: service@icpdas.com
24
Page: