SYSTem:RIN:STATe <Bool>
Function
Enables / Disables the internal resistance function.
Parameters
0|1, OFF|ON
Query
SYSTem:RIN:STATe?
Return
<Bool> 0|1
The Internal Resistance function can be set to ON only if the Sequencer, Constant Power Limit,
Analog Programming and Slew-Rate modes are disabled.
SYSTem:REMote[:STATe] <DSC>
Function
Sets the power supply control source (front panel or communication) to
local, remote, or LLO mode.
Local – Enables the front panel control.
Remote – Disables the front panel settings change.
LLO – same as remote + disable front panel unlock by the front panel.
Deactivates LLO only by communication or AC recycle.
Parameters
0|1|2 or LOC|REM|LLO
Query
SYSTem:REMote[:STATe]?
Return
<DSC> LOC|REM|LLO
System state changes from LOC to REM only if a communication command, which changes a
setting, is sent (Queries does not change system state to Remote mode). System state changes
from LLO to REM after AC power recycle.
SYSTem:SENSe[:STATe] <DSC>
Function
Selects the output sensing point - local or remote
Parameters
0|1, LOC|REM, OFF|ON
Query
SYSTem:SENSe[:STATe]?
Return
<DSC> LOC|REM
SYSTem:SLEW[:STATe] <DSC>
Function
Sets OFF / Voltage / Current reference slew control.
OFF – Slew control is disabled.
VOLT – Voltage reference slew control enabled.
CURR – Current reference slew control enabled.
Parameters
0|1|2 or OFF|VOLT|CURR
Query
SYSTem:SLEW[:STATe]?
Return
<DSC> OFF|VOLT|CURR
NOTE
NOTES
125