Mitsubishi Electric NZ2GFCE-60DAV8 User Manual page 104

Cc-link ie field network digital-analog converter module (e-con type)
Table of Contents

Advertisement

Initial data setting completed flag
■Device number
Signal name
Initial data setting completed flag
■Description
Initial data setting completed flag (RX9) turns on after the following actions are executed and the change of operating
conditions is completed.
1.
Write the parameter data to a remote buffer memory area using the REMTO instruction.
2.
Turn on Initial data setting request flag (RY9).
For the remote buffer memory areas that require Initial data setting request flag (RY9) to be turned on and off to enable written
parameter data, refer to the following:
Page 19 List of Remote Buffer Memory Areas
Module power supply
Initial data setting completion flag (RX9)
Initial data setting request flag (RY9)
Parameter area
Remote READY (RXB)
Executed by the D/A converter module
Executed by the program
(1) The setting is read from non-volatile memory.
(2) With Setting value A, action starts.
(3) The setting value is changed by the user.
(4) Action with Parameter setting value B starts in this timing.
*1 For data link to be made at the power-on of the module power supply
*2 When turning on and off Initial data setting request flag (RY9), check that Remote READY (RXB) turns on before starting the control.
APPX
102
Appendix 1 Details of Remote I/O Signals
Downloaded from
ManualsNet.com
ON
*1
OFF
OFF
OFF
*2
OFF
search engine
Device number
RX9
(1)
(3)
(Setting value A)
(Setting value B)
(Setting value B)
(2)
ON
ON
OFF
ON
OFF
(4)
ON
OFF