Mitsubishi Electric NZ2GFCE-60DAV8 User Manual page 129

Cc-link ie field network digital-analog converter module (e-con type)
Table of Contents

Advertisement

Cables
Use shielded cables for the cables which are connected to the module and run out from the control panel. If a shielded cable
is not used or not grounded correctly, the noise immunity will not meet the specified value.
■Cables for the CC-Link IE Field Network
CC-Link IE Field Network cables are made up of shielded wires. Strip a part of the jacket as shown below and ground the
exposed shield in the largest possible area.
(1) Cables for the CC-Link IE Field Network
(2) Shield
■Grounding the cable clamp
Use shielded cables for external wiring and ground the shields of the external wiring cables to the control panel with the
AD75CK cable clamp (manufactured by Mitsubishi Electric Corporation). (Ground the shield section 20 to 30cm away from
the module.)
(1)
AD75CK
(1) Module
(2) Inside a control panel
For details on the AD75CK, refer to the following:
 AD75CK Cable Clamping Instruction Manual
■Analog I/O signal line
Use a signal line of 30m or shorter when connecting it to the analog I/O terminals of the module.
External power supply
• Use a CE-marked product for an external power supply and always ground the FG terminal. (External power supply used
for the tests conducted by Mitsubishi Electric Corporation: TDK-Lambda DLP-120-24-1, IDEC PS5R-SF24, PS5R-F24)
• Use a power cable of 10m or shorter when connecting it to the module power supply terminal.
Downloaded from
ManualsNet.com
(1)
(2)
(2)
(2)
20 to 30 cm
search engine
Appendix 7 EMC and Low Voltage Directives
A
APPX
127