Mitsubishi Electric NZ2GFCE-60DAV8 User Manual page 98

Cc-link ie field network digital-analog converter module (e-con type)
Table of Contents

Advertisement

When the D LINK LED turns off
Check item
Does the own station in network operate normally?
Are 1000BASE-T-compliant Ethernet cables used?
Is the station-to-station distance 100m or less?
Does the cabling condition (bending radius) meet the specifications?
Is any Ethernet cable disconnected?
Do other stations connected to the D/A converter module operate
normally?
Does the switching hub normally operate?
Does the station number of the D/A converter module overlap with the
other stations?
When the D LINK LED flashes
Check item
Does the set station number of the D/A converter module match the
station number of the D/A converter module that is set up in the
network configuration settings of the master station or in the CC IE
Field configuration?
Is the station type remote device station?
Is the D/A converter module a reserved station?
Is stop of the data link checked through CC-Link IE Field Network
diagnostics?
Is the station number setting switch set to a value other than 1 to 120?
Has the connection been changed to the other master station with a
different network number?
When the L ER LED turns on
Check item
Are Ethernet cables normal?
Does the switching hub used in the system operate normally?
Do other stations connected to the D/A converter module operate
normally?
Is the mode of the master station set to other than Online?
Is there any noise affecting the system?
Is the loopback function enabled for the master station?
10 TROUBLESHOOTING
96
10.4 Checking the LEDs
Downloaded from
ManualsNet.com
search engine
Action
Connect the engineering tool to the master station, and then check if a data link is
established in the own station by using CC-Link IE Field Network diagnostics.
 User's manual for the master/local module used
Replace the cable with a 1000BASE-T-compliant Ethernet cable.
 User's manual for the master/local module used
Change the station-to-station distance to 100m or less.
Refer to the manual for the Ethernet cable used, and correct the bend radius.
Replace the Ethernet cable.
Check if the power supplies of the other stations are turned on.
• Check if a 1000BASE-T-compliant switching hub is used.
 User's manual for the master/local module used
• Check if the power supply of the switching hub is turned on.
Two or more stations are overlapping.
Change the setting so that all the station numbers differ.
Action
Match the station number of the D/A converter module with the station number that is
set up in the network configuration settings of the master station or in the CC IE Field
configuration.
In the network configuration settings of the master station, change the station type of
the module to the remote device station.
Change the setting of reserved/invalid error station to other than the reserved station
in the network configuration settings of the master station.
Check the link status through CC-Link IE Field Network diagnostics and start the link
when the data link is stopped.
The setting range for the station number setting switch is 1 to 120. Set a number from
1 to 120.
• Correct the connection to the previous master station.
• To communicate with a master station with a different network number, power off
and on the D/A converter module.
Action
• Check if 1000BASE-T-compliant Ethernet cables are used.
 User's manual for the master/local module used
• Check if the station-to-station distance is 100m or less.
• Check if the Ethernet cables are not disconnected.
• Check if a 1000BASE-T-compliant switching hub is used.
 User's manual for the master/local module used
• Check if the power supply of the switching hub is turned on.
Check if the power supplies of the other stations are turned on.
Change the mode of the master station to Online.
• Check the wiring condition of the Ethernet cables.
• Ground the control panel in which the D/A converter module was installed.
When the loopback function is enabled, check if the ring topology is correctly
configured for the port where the L ER LED is on.
 User's manual for the master/local module used