Function List - Mitsubishi Electric NZ2GFCE-60DAV8 User Manual

Cc-link ie field network digital-analog converter module (e-con type)
Table of Contents

Advertisement

2.3
Item
D/A conversion enable/disable function
D/A output enable/disable function
Range switching function
Analog output HOLD/CLEAR function
Cyclic data update watch function
Scaling function
Shift function
Digital value range check function
Alert output function
Error notification function
CC-Link IE Field Network diagnostic function
iQ Sensor Solution data backup/restoration
function
2 SPECIFICATIONS
16

2.3 Function List

Downloaded from
ManualsNet.com
Function List
Description
Allows D/A conversion to be enabled or disabled for each channel.
Disabling the D/A conversion for unused channels reduces the conversion
cycles.
Allows the selection of whether to output the D/A conversion value or the offset
value for each channel.
Whether the output is enabled or disabled, the conversion cycle is constant.
Allows the output range to be selected for each channel from the following:
• Voltage: 1 to 5V, 0 to 5V, -10 to 10V
• Current: 4 to 20mA, 0 to 20mA
Allows the selection of whether to hold or clear the analog value output when the
CPU module is in the following operating status: RUN, STOP, or a stop error.
Monitors the update intervals of cyclic data. For the cyclic transmission stop
lasting longer than the specified monitoring time, whether to hold or clear the last
output value can be selected.
Performs scale conversion on a digital value within the range of the scaling upper
limit value and the scaling lower limit value, both of which are set at desired
values. This function reduces the time and effort to create a program of the scale
conversion.
Provides analog output, adding the set shift value to a digital value. This function
facilitates fine adjustment at the system start-up.
Outputs an error when a digital value is out of the digital input range of the output
range setting.
Outputs an alert when a digital value falls within the alert output range set in
advance.
Notifies an error to the master station by the remote input signal if a moderate
error or a major error occurs in the D/A converter module.
Allows the presence or absence of a network error to be checked by accessing
the engineering tool connected to the CPU module.
Backs up such data as slave station setting data in the SD memory card in the
CPU module of the master station. Restores such data as setting data backed up
in the SD memory card of the master station CPU module into the slave station.
search engine
Reference
Page 53 D/A Conversion
Enable/Disable Function
Page 53 D/A Output
Enable/Disable Function
Page 54 Range
Switching Function
Page 55 Analog Output
HOLD/CLEAR Function
Page 57 Cyclic Data
Update Watch Function
Page 58 Scaling
Function
Page 62 Shift Function
Page 66 Digital Value
Range Check Function
Page 69 Alert Output
Function
Page 72 Error
Notification Function
Page 75 CC-Link IE Field
Network Diagnostic
Function
 iQ Sensor Solution
Reference Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gfce-60dai8

Table of Contents