6.4.6
Locate the device
Use the Locate Device function to identify this device by showing a pattern on the device
display, as illustrated in
Procedure
1. Select Service Tools → Maintenance → Routine Maintenance.
2. Select Locate Device and follow the on-screen instructions.
6.4.7
Run the install new power module setup
Run this setup when a new power module is installed.
Procedure
1. Select Service Tools → Maintenance → Routine Maintenance.
2. Select Install New Power Module and follow the on-screen instructions.
6.4.8
Perform a device reset
The Device Reset function re-starts electronics of the Rosemount 2160 without having to
cycle the power. It preserves the user-configuration.
Procedure
1. Select Service Tools → Maintenance, → Reset/Restore
2. Select Device Reset and follow the on-screen instructions.
6.4.9
Load user defaults
The Load User Defaults function resets the user-configuration to the ex-factory settings.
Procedure
1. Select Service Tools → Maintenance → Reset/Restore.
2. Select Load User Defaults and follow the on-screen instructions.
Rosemount 2160 Wireless Level Detector
Figure
6-1.
Figure 6-1: Locate Device Pattern
Service and troubleshooting
May 2022
65