Emerson Rosemount 2160 Reference Manual page 63

Wireless level detector
Hide thumbs Also See for Rosemount 2160:
Table of Contents

Advertisement

Reference Manual
00809-0100-4160
Counters
The Counters menu displays the following live counters:
Table 6-6: Counters Menu
Term
Sensor Wet Count
Calibration Count
Fault Count
Timers
The Timers menu displays the following live timers:
Table 6-7: Timers Menu
Term
Time Since Output Change
Total Time Dry
Total Time Wet
Number of Join Attempts
Note
Units for the timers are days, hours, minutes, and seconds. Seconds are not shown for long
times.
6.4.4
Dry fork calibration
This command starts the on-site calibration of the fork sensor in dry process conditions. It
should only be performed by authorized persons.
A comparison is made between the live fork sensor frequency measured in dry process
conditions and original factory-set Dry Fork Frequency value.
Rosemount 2160 Wireless Level Detector
Description
This counter increments each time the PV (Output State)
changes "dry" and "wet" state. Optionally, reset or preset it by
setting a new value using the Reset/Preset Wet Count
command.
The Rosemount 2160 is calibrated under reference conditions at
the factory. In special circumstances, it may be re-calibrated in
the field and this will increment the calibration count.
This counter increments each time there is a fault condition.
Optionally, reset the counter to zero using the Reset Fault Count
command.
Description
This is the time elapsed since the PV (Output State) variable last
changed to a "dry" or "wet" state. Optionally, this timer can be
reset to zero by editing the counter.
The total time that the PV (Output State) variable has been in a
'dry' state. Optionally, this timer can be reset to zero by editing
the counter.
The total time that the PV (Output State) variable has been in a
'wet' state. Optionally, this timer can be reset to zero by editing
the counter.
Number of times the device has tried to join the network prior to
being accepted. Too many join attempts result in the device
considering the join attempt as failed. If this happens, re-check
the Join Key and Network ID.