15.2 Error Message List

Error 05,
DIVIDE BY ZERO
Error 07,
SQUARE ROOT
Error 09,
LOG/LN
Error 16,
+15V SUPPLY HIGH
Error 17,
+15V SUPPLY LOW
Error 18,
-15V SUPPLY HIGH
Error 19,
-15V SUPPLY LOW
Error 20,
CHANNEL >MAXCH
Error 21,
BLOWN STACK
Error 22,
TYPE NOT FOUND
Error 23,
CAN'T RENDER FS
Error 24,
SIG.MOD CRC ROM
Error 25,
SIG.MOD CRC READ
Error 26,
NO SIG.MOD.
Error 27,
S.EE WRITE NAK
Error 28,
S.EE READ NAK
Error 29,
S.EE VERIFY FAIL
page 128
008-0671-00
A Mathematics Virtual channel has attempted to divide by zero.
A Mathematics Virtual channel has attempted to take the square root of a negative
number.
A Mathematics Virtual channel has attempted to take the logarithm of either zero or a
negative number.
The internal +15 VDC power supply is generating a voltage that is too high.
The internal +15 VDC power supply is generating a voltage that is too low. Check the
wiring between the instrument and the transducer or amplifier.
The internal -15 VDC power supply is generating a voltage that is too high (more pos-
itive). Check the wiring between the instrument and the transducer or amplifier.
The internal -15 VDC power supply is generating a voltage that is too low (more nega-
tive).
An invalid channel number has been encountered by the instrument. Restart the
instrument. If this error persists, contact our Service department with the information
found in the
->
SYSTEM MENU
The instrument's software stack has overflowed. Restart the instrument. If this error
persists, contact our Service department with the information found in the
>
menu item.
SOFTWARE REV.
The instrument has not been programmed to understand the type of channel. Contact
our Service department with the information found in the
menu item.
The full-scale value of the transducer cannot be rendered on the display with the
selected
menu settings. Change the
DISPLAY SETUP
match the transducer's capacity.
A checksum error occurred while reading a Signature Module's read-only-memory.
Check the wiring and restart the instrument. This error may occur with very long cable
lengths.
A checksum failure occurred reading data from a Signature Module. Check the wiring.
This error may be caused by a faulty Signature Module.
No Signature Module was detected during
wiring.
The channel's EEPROM could not be detected during a write operation. Restart the
instrument.
The channel's EEPROM could not be detected during a read operation. Restart the
instrument.
A verification failure occurred during a write operation to the channel's EEPROM.
menu item.
SOFTWARE REV.
DISPLAY SETUP
UPDATE SIG.MOD.
SYSTEM MENU
->
SYSTEM MENU
SOFTWARE REV.
menu settings to better
or
Check
DEFAULT SIG.MOD.
-