7800 SERIES S7800A1142 KEYBOARD DISPLAY MODULE
4. State 4: In the fourth state, both lines are blanked for
one-half second, then the display sequences to the first
state.

Hold and Fault Message Summary

Fault Code
Fault 1
No card is plugged into the
*No Purge Card*
purge card slot.
Fault 2
Excess noise or device running
*AC Frequen/Noise
on slow ac.
Fault 3
Ac line dropout detected.
*AC Line Dropout
Fault 4
Device running on fast ac.
*AC Frequency*
Fault 5
Low ac line detected.
*Low Line Voltage*
Fault 6
Purge card timing changed
*Purge Card Error*
since card was initially read.
Fault 7
Flame sensed when flame not
*Flame Amplifier*
present.
Fault 8
Flame sensed when no signal
*Flame Amp/Shutr*
expected during shutter-check
or Ampli-Check™ versions.
Fault 9
Flame sensed when no flame is
*Flame Detected*
expected during STANDBY.
Fault 10
Pre-Ignition Interlock fault
*Pre-Ignition ILK*
during STANDBY
65-0288-1
Table 7. Hold and Fault Message Summary.
System Failure
1. Make sure the purge card is seated properly.
2. Inspect the purge card and connector on the relay module for
3. Reset and sequence the relay module.
4. If the fault code reappears, replace the purge card.
5. Reset and sequence the relay module.
6. If the fault persists, replace the relay module.
1. Check the relay module and display module connections.
2. Reset and sequence the relay module.
3. Check the relay module power supply and make sure that both
4. Check the backup power supply, as appropriate.
1. Make sure the purge card is seated properly.
2. Inspect the purge card and connector on the relay module for
3.
4. If the fault code reappears, replace the purge card.
5. Reset and sequence the relay module.
6. If the fault persists, replace the relay module.
1. Check wiring and correct any errors. Make sure that the flame
2. Make sure that flame detector and flame amplifier are
3. Remove the flame amplifier and inspect connections. Reset
4. Reset and sequence the relay module.
5. If the code reappears, replace the amplifier.
6. If the fault persists, replace the flame detector.
7. If the fault persists, replace the relay module.
1. Check that flame is not present in the combustion chamber;
2. Check wiring and correct any errors. Make sure that flame
3. Remove the flame amplifier and inspect its connections. Reset
4. Reset and sequence the relay module.
5. If the code reappears, replace the amplifier and/or the flame
6. If the fault persists, replace the flame detector.
7. If the fault persists, replace the relay module.
1. Check wiring and correct any errors.
2. Check Pre-Ignition Interlock switches to assure proper
3. Check fuel valve operation.
4. Reset and sequence the relay module; monitor the Pre-Ignition
5. If the code persists, replace the relay module.
16
NOTE: For further explanation of Lockout Messages,
Troubleshooting and Checkout, refer to form 65-0229.
Recommended Troubleshooting
damage or contaminants.
frequency and voltage meed the specifications.
damage or contaminants.
Reset and sequence the relay module.
sensor wires are in separate conduits. Check for noise
coupling into the flame detector leadwires.
compatible.
the flame amplifier.
correct any errors.
sensor wires are in separate conduits. Check for noise
coupling into flame detector leadwires.
the amplifier.
detector.
functioning.
Interlock status.