Programming
Pressing 1 while viewing the Silenceable Screen #2 will program the selected Output as a SYNC
MUTE (synchronized mute) circuit. Refer to "Synchronized NAC Operation" on page 59 for a
description of synchronization.
Important: When an Output Circuit with a mix of audible and visual devices is programmed for
Sync Mute, only the audible devices will be turned off if the Silence key is pressed or if the
Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to operate.
NOTE: If the Output Circuit has been programmed as a Releasing Circuit, the Silenceable
Option will not be available and the display will indicate N/A next to it.

Auto Silence

The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable
notification appliances after a programmed length of time. To enable this feature and program the
time delay before Auto Silence activation, press 2 while viewing Output Screen #2. The following
screens will be displayed:
1=NO
2=5 MINUTES
3=10 MINUTES
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the display
will return to NAC Screen #1.
NOTE:
Option will not be available and the display will indicate N/A next to it.

Silence Inhibited

OUTPUT #
1=SILENCEABLE
YES
2=AUTO SILENCE
NO
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board
3=SIL INHIBITED NO
Output for a period of one minute. Resetting the FACP will also be prevented for one minute while
Output Screen #2
the Output programmed for silence inhibit is activated. Pressing 3 while viewing Output Screen #2
will cause a screen to be displayed with the options 1=No Silence Inhibit and 2=1 Min. Silence
Inhibit. Pressing 1 will disable the Silence Inhibit feature while pressing 2 will enable a 1 minute
Silence Inhibit for the selected Output.

Coding

OUTPUT #1=CODING
The Coding feature allows the programmer to select the type of output that the main circuit board
outputs will generate when activated. Pressing 1 while viewing Output Screen #3 will cause the
Output Screen #3
following displays to appear:
58
AUTO SILENCE
Auto Silence Screen #1
If the Output Circuit has been programmed as a Releasing Circuit, the Auto Silence
CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
CODING
1=CROSS ZONE
2=SYNC SYSTEM SENSOR
3=SYNC WHEELOCK
Coding Screen #3
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #2
CODING
1=TEMPORAL
2=FUTURE USE
3=FUTURE USE
Coding Screen #2
CODING
1=SYNC GENTEX
2=SYNC FARADAY
3=SYNC AMSECO
Coding Screen #4
MRP-2001 Series Manual — P/N 53040:H 1/26/2017
Master Programming Level
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #3