TROUBLESHOOTING
Alarm
A1
Description
The voltage or frequency of the input line are out of tolerance.
 Mains instability or failure.
Possible
causes
 Wrong phase rotation.
Solutions
Alarm
A2
Description
The phase rotation on the rectifier input line is wrong.
 Wrong connection of power cables.
Possible
causes
Solutions
Alarm
A3
Description
The rectifier has been temporarily disconnected and the inverter is fed by the
battery.
 Instability of the AC line voltage or frequency.
Possible
causes
 Possible fault in the rectifier control circuit.
Solutions
Alarm
A4
Description
The rectifier has been disconnected due to an internal fault.
 Possible fault in the rectifier control circuit.
Possible
causes
Solutions
procedures.
Manuel de l'utilisateur de l'ASI
MAINS FAULT
Check the connections to the mains.
Check the stability of mains voltage.
If the alarm persists, contact our Technical Support Service.
INPUT WRONG SEQ
Check the phase rotation.
If the alarm persists, contact our Technical Support Service.
BOOSTER STOPPED
Check the parameters of the AC line voltage.
Restart the device.
If the alarm persists, contact our Technical Support Service.
BOOSTER FAULT
Check which alarms are present and carry out the indicated
Restart the device.
If the alarm persists, contact our Technical Support Service.
UPS user manual
Utilizzo dell'UPS
OMW07104 REV.A
47