The UPS must be so installed as to ensure its serviceability and to allow a correct air flow as much as
possible.
With regard to the minimum distances from the walls, for all of the UPS sizes the same installation
conditions apply as indicated in the table below.
- UPS with internal batteries
Recommended clearances
Minimum clearances
E* valid only with internal battery
- UPS with external battery cabinet
Recommended clearances
Minimum clearances
The table below shows the air volume required for an optimal ventilation and cooling of the UPS.
28
OMW07096 REV. E
Installation and start-up of KEOR HPE UPS 60÷80 kVA
Installation et démarrage de l'ASI KEOR HPE 60÷80 kVA
Installazione e avviamento KEOR HPE UPS 60÷80 kVA
A (mm)
50
A (mm)
50
Power (kVA)
Air volume (m
3
/h)
B (mm)
1200
0
1200
B (mm)
1200
0
1200
60
1100
1000
C (mm)
D (mm)
E* (mm)
600
600
600
400
C (mm)
D (mm)
400
600
0
400
80