7.2.3 Communication bus monitoring
The second line of this menu gives a general indication regarding the communication between the UPS
units composing the system.
 The numbers represent the single UPS units.
 The letters M and S stand for MASTER and SLAVE respectively.
 The brackets [ ] around a letter indicate that we are working on that specific UPS unit.
 A question mark next to a number indicates that that UPS unit is not communicating on the data
bus.
7.2.4 Parallel type
The string on the second line may have two values, "POWER" or "REDUNDANT+x".
 POWER means that the parallel system is so set as to require the presence of all the UPS units
to feed the load.
 REDUNDANT+x means that the system is redundant and the redundancy index is indicated by
number "X". For example, in a system composed of 2 UPS units, "REDUNDANT+1" means that
only one of the UPS units is sufficient to feed the load.
7.2.5 Message statistics
The statistics section regarding the messages exchanged on the communication buses consists of two
different menus.
Number of messages received and percentage of reception accuracy regarding the synchronism signals.
The messages are sent by the MASTER UPS, therefore the number will only increase on the SLAVE UPS
units.
Number of messages received and percentage of reception accuracy regarding the status of the system.
The messages are exchanged between all the UPS units, therefore the number will increase on all of them.
SERVICE INFORMATION
The SERVICE menu provides important information regarding the technical service on the UPS.
The information is displayed via a text string of max. 60 characters which scrolls on the second display line.
However, please also see the addresses and contact numbers indicated in the present manual.
UPS user manual
Manuel de l'utilisateur de l'ASI
PARALLEL RECTIFIER
1-[ M ]
2- S
PARALLEL
REDUNDANT+x
CAN STATISTICS RAD
SYNC RX: 15849
CAN STATISTICS RAD
MSG RX: 9277
Utilizzo dell'UPS
100.0%
99.9%
OMW07104 REV.A