Setting all the parameters
To save all the parameters it is necessary to reach the end of the guided procedure until
the last screen previously shown.
If the procedure is interrupted earlier, none of the parameters previously set will be saved.
SETTING THE MODBUS PARAMETERS
The parameters regarding the communication via RS485 interface can be set in the MODBUS menu.
 Modbus address
MODBUS ADDRESS
202
Parameter
MODBUS ADDRESS
UPS TEST
The UPS TEST menu allows to carry out a switching test of the inverter. The inverter is switched off and
the load is transferred to the bypass supply. The inverter supply is automatically restored after a few
seconds.
UPS TEST?
UPS TEST?
YES
SPECIAL
UPS TEST
Possible loss of supply
In case of power failure while the test is being performed, the immediate operation of the
inverter is not guaranteed.
36
OMW07104 REV. A
UPS user manual
Manuel de l'utilisateur de l'ASI
Utilizzo dell'UPS
Standard
1
NO
(1x)
The single digits can be modified via the arrow
keys (
/
) and confirmed by pressing
(ENTER).
Range
1 .... 247
The value on the second line is ready to be
changed
The parameter is changed. The change is
confirmed by pressing
The system performs a test and returns to the
previous screen
(ENTER)