Download Print this page

LEGRAND KEOR HPE 60 kVA Operating Manual page 1394

Hide thumbs Also See for KEOR HPE 60 kVA:

Advertisement

Available languages

Available languages

Keor HPE
60-80-100-125-160-200-250-300-400-500
Conventional UPS - Online three-phase double conversion VFI
n
Characteristics
General specifications
Apparent power (kVA)
Active power (kW)
UPS architecture
Input
Input voltage
Input frequency
Input voltage range
THD Input Current
Compatibility with power supply units
Input power factor
Output
Output voltage
Output frequency (apparent)
THD Output Voltage
Output voltage tolerance
Overload capacity
Efficiency in Eco Mode
Batteries
Internal battery
Autonomy expansion
Battery series type
Battery charger
Communication and management
Communication ports
Alarms and signals
Emergency Power Off (EPO)
Remote management
Battery temperature probe
Mechanical Features
Dimensions (H x L x D) (mm)
Net weight (kg)
Ambient Conditions
Operating temperature (°C)
Relative humidity (%)
Protection rating
Noise at 1 mt from the unit (dBA)
Conformity
Certifications
8
60
80
60
80
60
80
Technology
Waveform
Efficiency
Up to 95%
Crest factor
10 minutes at 125%, 30 seconds
at 150% 0.1 seconds >150%
Bypass
yes
yes
Battery test
LCD and LED display for real-time monitoring
LCD display
of the UPS status 4 buttons for menu navigation
(7" touch display optional)
1500 x 560 x 940
225
250
100
125
160
100
125
160
100
125
160
On-Line Double Conversion VFI-SS-111
Sinusoidal
Conventional UPS with parallel capacity up to 6 units
380-400-415 V 3Ph+N
50-60 Hz (45-65Hz)
400 V -20% / + 15%
< 3%
Configurable to achieve synchronism between the input
and output frequencies also for larger frequency ranges
> 0.99
380, 400, 415 V 3Ph+N
Up to 96%
50 /60 Hz
3:1
<1% (with linear load), <5% (with non-linear load)
± 1% (with balanced load)
10 minutes at 110%, 5 minutes at 125%, 30 seconds
> 98%
Automatic and maintenance bypass
-
-
-
Yes with additional battery cabinets
VRLA - AGM Lead-acid, sealed, maintenance-free
Automatic or manual
IU (DIN41773)
relay contact board, RS232, USB,
Net Interface Slot (Optional: Mod-Bus RS485, SNMP-Ethernet)
Configurable acoustic alarms and signals
yes
available
yes
1800 x 560 x 940
320
360
380
0 - 40
< 95% non condensing
IP20
< 60
EN 62040-1, EN 62040-2, EN 62040-3
200
250
300
400
200
250
300
400
200
250
300
400
Up to 96.4%
at 150%, 0.1seconds >150%
-
-
-
10" touch-screen display to monitor
UPS status in real-time
1975 x 850 x 966
1978 x 1430 x 970
720
850
900
1080
< 65
500
500
500
-
-
1250
< 72dB

Advertisement

loading