LED'S BAR
Picture 10 – LED's bar
LED 11
LED 12
LED 13
LED 14
LED 15
24
OMW07104 REV. A
UPS user manual
Manuel de l'utilisateur de l'ASI
Utilizzo dell'UPS
AC line on rectifier input within tolerance
GREEN
Wrong phase rotation (fast blinking)
GREEN
Unbalanced AC voltage (slow blinking)
GREEN
AC mains failure
OFF
Circuit breaker BCB closed and battery charging
GREEN
Battery discharging or under TEST (fast blinking)
ORANGE
Circuit breaker BCB open (slow blinking)
ORANGE
End of battery autonomy / Battery fault
RED
Inverter voltage within tolerance and static switch closed
GREEN
Inverter overload or short-circuit
ORANGE
Inverter critical alarm
RED
Inverter off
OFF
AC bypass line within tolerance
GREEN
Wrong phase rotation (fast blinking)
RED
AC bypass line out of tolerance / failure
RED
Programmed maintenance required (slow blinking)
GREEN
Critical alarm (fast blinking)
GREEN

Advertisement