9.3.4 Cleaning the condenser

9.3.4.1 Air-cooled condenser

Caution!
The SmartCool System refrigerating machine operates largely without servicing.
So that the full cooling power is available, the heat exchanger (condenser) should cleaned of dust at intervals of one
month or longer depending on the operating period and dust level in the ambient air.
9.3.4.2

Water-cooled condenser

9.3.4.2.1

Cleaning the dirt trap

At regular intervals of one month or longer, the dirt trap must be cleaned, depending on the degree of soiling.
03/2022
Contact with sharp slats on the condenser
during cleaning
Clean the condenser using suitable resources such as a hand
brush or compressed air.
To do this, open the front grille, brush off the condenser and,
where necessary, blow over with compressed air.
Extreme contamination is detected by the Proline SelfCheck
Assistant, which then issues a warning.
Take off the water feed hose on the device and remove the
filter. Clean the filter and insert it again into the cooling water
feed.