Programming; Ul 864 Programming Requirements; Section 6 Programming - Honeywell Silent Knight INTELLIKNIGHT 5600 Installation And Operation Manual

Addressable fire control panel
Table of Contents

Advertisement

Section 6

Programming

This section of the manual describes how to change the control panel programming options
from the built-in web page of the control panel. All options described in this section are edited
via the panel's built in web page
Before any customized programming is done, JumpStart should be run first. After
JumpStart is run, thoroughly test the system. The reason the system should be tested
after JumpStart is because JumpStart automatically programs the system, searching for
and configuring all SLC devices and SBUS annunciators it finds. JumpStart allows you
to confirm the integrity of the installation prior to performing any custom
programming. After determining that the hardware is properly installed, custom
programming can be performed. Refer to Section 6.
6.1

UL 864 Programming Requirements

Table 6-1: Standards in Requirements for Control Units and Accessories
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES: This product incorporates field programmable software. In
order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Programming Option
System Options
Zone Options
Zone Options
System Options
Dialer Phone line Programming
option
*Only needs to be enabled if using the DACT.
151450
Important!
Permitted in
Menu Item
UL 864 (Y/N)
Low AC Report Delay
Supervisory
Waterflow
Alarm Verification
Line Monitor Enabled
Possible
Settings
Yes
0–30 hours
Yes
Latching/Non
Yes
Latching/Non
Yes
1-250 seconds
Yes
Y/N
Settings Permitted in
UL 864
1–3
Latching
Latching
60-250 seconds
Y*
6-1