Model
GD800-51-0810-6-S
GD800-51-0910-6-S
GD800-51-1025-6-S
GD800-51-1270-6-S
GD800-51-1481-6-S

2.4 Derated application

2.4.1 Derating due to temperature

The standard ambient temperature of inverter unit is in the range of +40℃ ~ +50℃, and the rated output
current of inverter unit must be derated by 1% for every 1℃ increase when the temperature exceeds 50℃.
The current reference value multiplied by the derating coefficient (k
temperature higher than 50℃.

2.4.2 Derating due to altitude

The inverter unit needs to be derated by 1% for every increase of 100m when the altitude exceeds 1000m.
Contact our local technical support for model selection when the altitude exceeds 2000m.
202202 (V1.0)
700–1035VDC (Rectifier incoming voltage: 3PH 520–690VAC)
Light overload
Rating
I
I
P
N
max
N
A (AC)
A (AC)
kW
A (AC)
810
1185
800
910
1320
900
1025
1500
1000
1270
1845
1200
1481
2165
1400
Figure 2-3 Derating due to temperature
k
e
1.00
0.90
0.80
Figure 2-4 Derating due to altitude
k
h
1.00
0.70
0.60
Heavy
overload
application
application
I
P
I
P
Ld
Ld
Hd
Hd
kW
A (AC)
kW
790
800
724
710
880
900
814
800
1000
1000
917
900
1230
1200
1136
1000
1405
1400
1320
1200
+40
+50
1000m
4000m
Product overview
Heat
dissipation
volume
Structure
kW
m³/h
A8s
11.5
A8s
11.7
A8s
13.2
A8s
16
A8s
18.2
) is the output current at the
e
T
T
Air
3900
3900
3900
3900
3900
8