Connecting redundancy connections (fiber-optic cables)

7.9.1.1

Synchronization modules for S7-1500H

Introduction
You use the synchronization modules to create two redundancy connections between the
two H-CPUs. You need two identical synchronization modules per CPU which you connect
with fiber-optic cables.
View
Figure 7-8  Synchronization module
Maximum cable length (fiber-optic cable) between the two H-CPUs
In the S7-1500H redundant system, you need to use four synchronization modules of the
same type. You can order the following types of synchronization modules:
Maximum cable lengths between the two H-
CPUs
10 m
10 km (minimum length: 2 m)
40 km (minimum length: 8 km)
7.9.1.2

Selecting fiber-optic cables

Introduction
You can find an overview of fiber-optic cables, the necessary conditions and technical
specifications in the system manual Industrial Ethernet/PROFINET Passive network compon­
ents (https://support.industry.siemens.com/cs/ww/en/view/84922825).
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
7.9 Connecting interfaces for communication with S7-1500H
Article number
6ES7960-1CB00-0AA5
6ES7960-1FB00-0AA5
6ES7960-1FE00-0AA5
Wiring
183