Item
Enter the start I/O number of the Simple Motion
Start I/O No.
module in increments of 16 points.
Enter the network number of the Simple Motion
Network No.
module.
• One master station can be set.
Set the total number of stations in a network
(excluding the master station).
• If any reserved station is required, include the
The number can be set when "CC IE Field (Motion
Total Stations
Master Station)" is selected in "Network Type".
When the checkbox next to "Set the network
configuration setting in the CC IE Field configuration
window" is selected, the setting value in the CC IE
Field configuration window is displayed.
Enter the station number of the Simple Motion
module. Set a station number different from those
Station No.
used in the same network.
The station number of the master station is fixed to
"0".
• For the master station
Set a master station mode.
Online
Mode
(Normal Mode)
Offline
Description
number of reserved stations.
Mode
Description
This mode performs cyclic
transmission and transient
transmission without losing their
inherent speed performance. This
mode is suitable for a system that
performs I/O control and analog
control, and transmits large
amount of data for management,
monitoring, and diagnostics by
transient transmission.
Use this mode for general
applications.
Select this mode to disconnect the
Simple Motion module from the
network for stopping data link with
other stations.
Chapter 7 PARAMETER SETTING
Setting range
Within the number of I/O points of the
CPU module (Default: Blank)
1 to 239 (Default: Blank)
• Master station:
1 to 120 (Default: Blank)
Master station: Fixed to "0"
• Online (Normal Mode)
• Offline
(Default: Online (Normal Mode))
7 - 6
Remark
•If the value
outside the
setting range is
set, "Parameter
error (error code:
D303H)" will
occur, and the
Simple Motion
module will start
in offline mode.