Error code
Own station No. not set (dedicated
D211H
instruction)
D212H
Transient transmission failed
D213H
Transient data command error
D214H
Transient data length error
D215H
Transient data request error
D216H to D217H
Transient data command error
Incorrect number of read/write
D218H
transient data
D219H
Transient data attribute code error
D21AH
Transient data access code error
D21BH to D21CH
Transient data request error
D222H
Transient data command error
D223H
Transient error
Station No. setting not available for
D22EH
the target station
No baton pass executed in the
D22FH
target station
D230H
Invalid station No. setting
Station No. already set in the target
D231H
station
D232H
Station No. setting target not exist
D233H
Station No. setting out of range
D234H
No baton pass executed
D235H
Transient error
Error
Set the station number in the parameter setting, and retry the operation.
• Check if the switching hub and the cables at the request source are
connected properly.
• Reduce the frequency of transient transmission, and retry the operation.
Correct the request command at the request source, and retry the
operation.
Correct the data length at the request source, and retry the operation.
Change the mode to Online, and retry the operation.
Correct the request command at the request source, and retry the
operation.
Correct the number of read/write device data at the request source, and
retry the operation.
Correct the attribute code at the request source, and retry the operation.
Correct the access code at the request source, and retry the operation.
• Abnormal transient data were issued from the CPU module.
• Replace the CPU module and retry the operation.
• If this error persists, please consult your local Mitsubishi service center or
representative.
Correct the request command at the request source, and retry the
operation.
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• If this error persists, please consult your local Mitsubishi service center or
representative.
• Although change of the target station number was attempted online from
the master station, the target station does not have the online station
number setting function.
• Check the manual for the target station if the station number setting
function is available.
• If the function is supported by the model, please consult your local
Mitsubishi service center or representative.
Check the communication status of the station whose station number is to
be changed.
• The station number change was attempted for the own station.
• Check that no station number is set for the target station.
• The station number has been already set for the target station.
• Check that no station number is set for the target station.
• The station where the station number change was attempted does not
exist.
• Check that no station number is set for the target station.
Set the station number within 1 to 120, and retry the operation.
Check the communication status.
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• If this error persists, please consult your local Mitsubishi service center or
representative.