Product overview
Overview of connections and plug
Bus node
Connection technology
CPX-FB33/43
2 x M12, D-coded, female, 4-pin, in
accordance with IEC 61076-2
CPX-M-FB34/44
2 x RJ45, push-pull, Cu, AIDA,
in accordance with IEC 60603,
IEC 61076-3
CPX-M-FB35/45
2 x SCRJ, push-pull, 650 nm, AIDA, in
accordance with IEC 61754-24
Tab. 11: Connection technology and network connectors
In the following table, the cable lengths were used in accordance with the specifications for PROFINET
networks.
Network connectors
NECU-MS-D12G4-C2-ET
FBS-RJ45-PP-GS
FBS-SCRJ-PP-GS
Tab. 12: Cable specification for network connectors
Service interface
An operator unit such as CPX-MMI-1 can be connected to the service interface.
Alternatively, the service interface can be connected to a PC via the USB adapter NEFC-M12G5-0.3-
U1G5 so that the "Festo Maintenance Tool" software (FMT) can be used.
12
Cable specification
Ethernet cable, shielded, Cat 5/5e, 6 ... 8 mm, 0.14 ... 0.75 mm
max. 100 m PROFINET end-to-end link: 22 AWG
Ethernet cable, shielded, Cat 5/Cat 5e, 5 ... 8 mm,
≙ ca. 26 ... 22 AWG;
0.13 ... 0.36 mm
2
max. 100 m PROFINET end-to-end link: 22 AWG
POF fibre-optic cable, 980/1000 µm, 6.5 ... 9.5 mm;
max. 50 m PROFINET end-to-end link; ≤ 12.5 dB
Festo — CPX(-M)-FB33/34/35/43/44/45 — 2022-05f
Network connectors
NECU-MS-D12G4-C2-ET
FBS-RJ45-PP-GS
FBS-SCRJ-PP-GS
;