AUMA SQVEx 05.2 Manual page 91

Part-turn actuators
Hide thumbs Also See for SQVEx 05.2:
Table of Contents

Advertisement

SQVEx 05.2
SQVEx 14.2/ SQRVEx 05.2
ACVExC 01.2 Modbus RTU
Features and functions
Fieldbus interface with additional
input signals (option)
Control voltage/current consumption
for control inputs
Status signals
Fieldbus interface with additional
input signals (option)
Voltage output
Redundancy (option)
SQRVEx 14.2 Control unit: electronic (MWG)
2 free analogue inputs (0/4
-
Signal transmission is made via Fieldbus interface
Inputs OPEN, STOP, CLOSE, EMERGENCY, I/O interface, MODE (via opto-isolator thereof OPEN,
STOP, CLOSE, MODE with one common and EMERGENCY, I/O interface respectively without
common)
-
Control inputs: OPEN, STOP, CLOSE, EMERGENCY
-
I/O interface: Selection of control type (Fieldbus or additional input signals)
-
MODE: Selection between open-close duty (OPEN, STOP, CLOSE) or modulating duty (0/4
20 mA position setpoint)
-
Additionally 1 analogue input (0/4
Inputs OPEN, STOP, CLOSE, EMERGENCY, I/O interface, MODE (via opto-isolator thereof OPEN,
STOP, CLOSE, MODE with one common and EMERGENCY, I/O interface respectively without
common)
-
Control inputs: OPEN, STOP, CLOSE, EMERGENCY
-
I/O interface: Selection of control type (Fieldbus or additional binary OPEN, STOP, CLOSE input
signals)
-
MODE: Selection between OPEN - CLOSE control and setpoint control (0/4
-
Additionally 1 analogue input (0/4
mA) for actual process value
Standard
24 V DC, current consumption: approx. 10 mA per input
Options:
48 V DC, current consumption: approx. 7 mA per input
60 V DC, current consumption: approx. 9 mA per input
100 V
125 V DC, current consumption: approx. 15 mA per input
100 V
120 V AC, current consumption: approx. 15 mA per input
All input signals must be supplied with the same potential.
Via Modbus RTU interface
Additional, binary output signals (only available in combination with additional input signals (option))
6 programmable output contacts:
-
5 potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive load)
Default configuration: End position CLOSED, end position OPEN, selector switch REMOTE,
torque fault CLOSE, torque fault OPEN
-
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
Default configuration: Collective fault signal (torque fault, phase failure, motor protection tripped)
6 programmable output contacts:
-
5 potential-free change-over contacts with one common, max. 250 V AC, 1 A (resistive load)
-
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
6 programmable output contacts:
-
6 potential-free change-over contacts without one common, max. 250 V AC, 5 A (resistive load)
6 programmable output contacts:
-
4 mains failure proof potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive
load), 1 potential-free NO contact, max. 250 V AC, 1 A (resistive load), 1 potential-free change-
over contact, max. 250 V AC, 5 A (resistive load)
6 programmable output contacts:
-
4 mains failure proof potential-free NO contacts, max. 250 V AC, 5 A (resistive load), 2 potential-
free change-over contacts, max. 250 V AC, 5 A (resistive load),
Analogue output signal for position feedback
-
Galvanically isolated position feedback 0/4
Standard:
Auxiliary voltage 24 V DC: max. 100 mA for supply of control inputs, galvanically isolated
from internal voltage supply.
Option:
Auxiliary voltage 115 V AC: max. 30 mA for supply of control inputs, galvanically isolated
from internal voltage supply
Redundant line topology with universal redundancy behaviour according to AUMA redundancy I or II
Redundant loop topology in combination with SIMA Master Station
Max. number of actuators with actuator controls per redundant loop: 247 units
Max. possible cable length between the actuators equipped with actuator controls without external
repeater: 1,200 m
Max. possible total length per redundant ring: approx. 290 km
Automatic commissioning of the redundant ring by means of the SIMA Master Station
20 mA), 4 free digital inputs
20 mA) for position setpoint
20 mA) for setpoint position and 1 analogue input (0/4
20 mA (load max. 500 Ω)
Technical data
20 mA)
20
91