SQVEx 05.2
Corrective action
Faults and warnings via status indications in the display
Indication on display
S0009
Function check
S0010
Maintenance required
S0011
Failure
Table 29:
Warnings and Out of specification
Indication on display
Config. warning
Internal warning
24 V DC external
Wrn op.mode run time
Wrn op.mode starts
Failure behav. active
Wrn input AIN 1
Wrn input AIN 2
Wrn setpoint position
Op. time warning
Wrn controls temp.
Time not set
RTC voltage
PVST fault
78
SQVEx 14.2/ SQRVEx 05.2
Description/cause
Collective signal 08:
Indication according to NAMUR recommendation
NE 107
The actuator is being worked on; output signals are
temporarily invalid.
Collective signal 09:
Indication according to NAMUR recommendation
NE 107
Recommendation to perform maintenance.
Collective signal 10:
Indication according to NAMUR recommendation
NE 107
Actuator function failure, output signals are invalid
Description/cause
Collective signal 06:
Possible cause:
Configuration setting is incorrect.
The device can still be operated with restrictions.
Collective signal 15:
Device warnings
The device can still be operated with restrictions.
The external 24 V DC voltage supply of the controls
has exceeded the power supply limits.
Warning on time max. running time/h exceeded
Warning on time max. number of motor starts
(starts) exceeded
The failure behaviour is active since all required
setpoints and actual values are incorrect.
Warning: Loss of signal analogue input 1
Warning: Loss of signal analogue input 2
Warning: Loss of signal setpoint position
Possible causes:
For an adjusted setpoint range of e.g. 4
the input signal is 0 (signal loss).
For a setpoint range of 0
20 mA , monitoring is
not possible.
The set time (parameter Perm.op. time, manual
M0570) has been exceeded. The preset operating
time is exceeded for a complete travel from end
position OPEN to end position CLOSED.
Temperature within controls housing too high.
Real time clock has not yet been set.
Voltage of the RTC button cell is too low.
Partial Valve Stroke Test (PVST) could not be suc-
cessfully completed.
SQRVEx 14.2 Control unit: electronic (MWG)
ACVExC 01.2 Modbus RTU
Remedy
For indicated value > 0: Press push button
tails.
For details, refer to <Not ready REMOTE and
Function check> table.
For indicated value > 0: Press push button
to display a list of detailed indications.
For indicated value > 0: Press push button
to display a list of detailed indications.
For details, refer to <Faults and Failure> table.
Remedy
Press push button
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Press push button
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Check 24 V DC voltage supply.
Check modulating behaviour of actuator.
Check parameter Perm. run time M0356, re-set
if required.
Check modulating behaviour of actuator.
Check parameter Permissible starts M0357, re-
set if required.
Verify signals:
Setpoint E1
Actual value E2
Actual process value E4
Check connection to master.
Check wiring.
Check wiring.
Check setpoint signal.
20 mA,
The warning indications are automatically cleared
once a new operation command is executed.
Check valve.
Check parameter Perm.op. time, manual
M0570.
Measure/reduce ambient temperature.
Set time.
Replace button cell.
Check actuator (PVST settings).
De-
Details
Details
Details to display a list of indi-
Details to display a list of indi-