Honeywell Silent Knight SKE Series Installation And Operation Manual page 30

Voice evacuation
Table of Contents

Advertisement

SKE-SeriesVoice Evacuation System Installation/Operation Manual
DIP
Function
Switch
1
SW2
Evacuation
off
Tone Pattern
on
off
on
off
on
off
on
Local Mic.
Supervision
Selection
Remote Mic
CMD1 uses
recorded
message
CMD2 uses
recorded
message
Enter Record
Mode
4-2
Table 4-1: DIP Switch Programming
Switch Number
2
3
4
5
6
off
off
off
off
on
off
on
off
off
on
off
on
on
on
on
on
off
on
off
on
off
on
firealarmresources.com
Setting
7
8
ANSI Cadence
March Code
California
Steady
Alert Tone
Hi-Lo
ANSI Whoop
Continuous Whoop
Not supervised
Supervised
Not supervised
Supervised
Play Pre-recorded
CMD1 message
Play Recorded
Message
off
Play Pre-recorded
CMD2 message
on
Play Recorded
Message
off
on
Comments
This option selects the
tone sound that will be
made during
evacuation.
For UL 864
installations, this
option must be set to
ANSI cadence.
This selection
determines if the local
microphone will be
supervised.
For UL 864
installations, this
option must be set to
ON. OFF is not
acceptable for UL 864
installations.
This selection
determines if the
remote microphone
will be supervised.
For UL 864
installations, this
option must be set to
ON. OFF is not
acceptable for UL 864
installations.
This option selects
which message will be
played for CMD1 or
CMD2, either the pre-
recorded or the
recorded message.
151267