8.2.4
Connecting the SKE-V70 to the SKE-ZN4 or -ZN6
If the optional 4 or 6 zone splitter is used in the system connect the wire harnesses as follows:
1. Connect one harness from the main control to the SKE-V70 connector marked "FROM
CONTROL". See Figure 8-6.
2. Connect the other harness from the SKE-V70 connector marked "TO SPLITTER" to the
connector on the 4 or 6 zone splitter as shown in Figure 8-6.
SKE-450
Figure 8-6 Wire Harness Connections for Splitter and Main Control
Notes:Refer to Section 5 for SKE-ZN4 installation and wiring instructions. Refer to Section 6 for SKE-ZN6
installation and wiring instructions.
Speaker outputs of SKE-450 and the SKE-V70 must not be used when using either SKE-ZN4/-ZN6 in
combination with SKE-V70 because supervision will not be provided at the SKE-450 and the SKE-V70.
151267
SKE-V70
firealarmresources.com
SKE-V70 Module Installation
SKE-ZN4/-ZN6
15 kΩ EOL
UL Listed
Model 7630
8-5