4. Mount the SKE-ZN4 to the SKE-450 cabinet mounting standoffs with the 7/10" screw-in
standoffs provided.
Figure 5-4 SKE-ZN4 Mounting Standoff Locations
5. Connect wiring harness to the expansion connector on the SKE-450 and to the direct
connect pins on the SKE-ZN4. See Figure 5-5.
6. Wire speaker to zone outputs as required by installation specifications. See Section 5.4.
7. Attach the SKE-ZN4 cover plate to the SKE-ZN4. See Figure 5-5.
5-6
Wiring Harness (P/N 130398)
Figure 5-5 View With SKE-ZN4 Installed
firealarmresources.com
SKE-ZN4
Mounting
Standoffs
SKE-ZN4
Cover Plate
15 kΩ EOL
UL Listed
Model 7630
Speaker outputs of the SKE-450
must not be used with the SKE-ZN4
because supervision will not be
provided at the SKE-450.