SKE-Series Voice Evacuation System Installation/Operation Manual
6.1.3
Terminal Strip 3
This sections describes what the terminal connections of terminal strip 4 are used for.
Terminal Name
Not Used
+
Speaker 3 return positive connection, used for Class A (Style Z) configuration.
IN3
Speaker 3 return negative connection, used for Class A (Style Z) configuration.
+
Speaker output 3 positive connection, used for Class B (Style Y) configuration.
OUT3
Speaker output 3 negative connection, used for Class B (Style Y) configuration.
+
Speaker 2 return positive connection, used for Class A (Style Z) configuration.
IN2
Speaker 2 return negative connection, used for Class A (Style Z) configuration.
+
Speaker output 2 positive connection, used for Class B (Style Y) configuration.
OUT2
Speaker output 2 negative connection, used for Class B (Style Y) configuration.
+
Speaker 1 return positive connection, used for Class A (Style Z) configuration.
IN1
Speaker 1 return negative connection, used for Class A (Style Z) configuration.
+
Speaker output 1 positive connection, used for Class B (Style Y) configuration.
OUT1
Speaker output 1 negative connection, used for Class B (Style Y) configuration.
6.1.4

Manual Zone Switches

Manual zone switches are used to manually override the system message, using the
microphone, by zone.
For example, if you wish to manually give an evacuation message (using the microphone) to
zone 4, you would turn on switch 4, then key the microphone and speak the desired message.
Your manually-spoken message would be output to the speakers in zone 4 only.
6.1.5

All Call Switch

The All Call Switch manually overrides the system message, using the microphone, to all
zones in the system.
6.1.6

LED Descriptions

The SKE-ZN6 has two LEDs for each zone, an Active and a Trouble LED. The Active LED
(Red) indicates that the zone is activated when it is ON. The Trouble LED (Yellow), when on,
indicates that it does not detect the 15 kΩ end of line resistor on the speaker loop.
6-4
Description