Terminal Strip 1; Terminal Strip 2 - Honeywell Silent Knight SKE Series Installation And Operation Manual

Voice evacuation
Table of Contents

Advertisement

SKE-Series Voice Evacuation System Installation/Operation Manual
3.3.2

Terminal Strip 1

Terminal Name
+
-
Active
IN
Neg
In
Enable
FO
Com
NC
NO
Com
NC
NO
3.3.3

Terminal Strip 2

Terminal Name
+
CMD2
IN
+
CMD1
IN
+
CMD1
OUT
+
SPK IN Used for Class A (Style Z) speaker connections
+
SPK
OUT
3-4
Table 3-2: Terminal Strip 1 Description
Remote Microphone See Section 7.3.2 for details.
Aux Audio (Input)
For recording custom message only. See Section 4.2.2.
Not Used
AC Trouble (Relay) Form C energizes when an AC trouble is detected regardless of
setting of the AC delay switch.
Trouble (Relay)
Form C common trouble relay
Table 3-3: Terminal Strip 2 Description
A short across this input will activate message 2.
A reverse polarity trip from the FACP will activate message 1.
Used for Class B (Style Y) and Class A (Style Z) speaker connections.