Class B (Style Y); Class A (Style Z) - Honeywell Silent Knight SKE Series Installation And Operation Manual

Voice evacuation
Table of Contents

Advertisement

SKE-Series Voice Evacuation System Installation/Operation Manual
6.4.2

Class B (Style Y)

Figure 6-5 illustrates how to wire speakers to the control panel using Class B (Style Y)
supervision.
15 kΩ EOL
UL Listed
Model 7630
Figure 6-5 Class B (Style Y) Speaker Configuration
Note:
Figure 6-5 uses Speaker Loop 5 as an example of the wiring. All other speaker loops are configured in
the same manner to their respective OUT terminals.
6.4.3

Class A (Style Z)

Figure 6-6 illustrates how to wire speakers to the control panel using Class A (Style Z)
supervision.
Figure 6-6 Class A (Style Z) Speaker Configuration
Note:
Figure 6-6 uses Speaker Loop 1 as an example of the wiring. All other speaker loops are configured in
the same manner to their respective terminals.
6-8
Supervised
Power Limited
firealarmresources.com
Supervised
Power Limited
151267