Speaker Wiring; Wiring Procedure - Honeywell Silent Knight SKE Series Installation And Operation Manual

Voice evacuation
Table of Contents

Advertisement

6. Connect wiring harness to the expansion connector on the SKE450 and to the direct
connect pins on the SKE-ZN6. See Figure 6-4.
7. Wire speaker to zone outputs as required by the installation specifications. Refer to
Section 6.4.
8. Attach the SKE-ZN6 cover plate to the SKE-ZN6. See Figure 6-4.
Note: Speaker outputs of the SKE-450 must not be used when using the SKE-ZN6 because supervision will not be
provided at the SKE-450.
6.4

Speaker Wiring

Each SKE-ZN6 supplies six NACs (Notification Appliance Circuits) for speaker connection.
The speaker circuits can be supervised and wired Class B (Style Y) or Class A (Style Z). Each
speaker circuit is capable of 20 watts of power.
Note:
This configuration illustrates a 25V installation if using an SKE-V70. For 70.7V installations, see Sec-
tion Section 8.
6.4.1

Wiring Procedure

In order to gain access to the terminals on the SKE-ZN6, the cover plate must be removed.
See Figure 6-4.
151267
Wiring Harness (P/N 130427)
Figure 6-4 View With SKE-ZN6 Installed
firealarmresources.com
SKE-ZN6 Six Zone Splitter Installation
SKE-ZN6
Cover Plate
15 kΩ EOL
UL Listed
Model 7630
6-7