Facp Alarm Zone Control Wiring - Honeywell Silent Knight SKE Series Installation And Operation Manual

Voice evacuation
Table of Contents

Advertisement

6.4.4

FACP Alarm Zone Control Wiring

This section describes how to connect relay outputs from a FACP to control the six separate
zones on the SKE-ZN6 six zone splitter.
Connect an active low relay or contact from the FACP to the Alarm Selects on the SKE-ZN6
(see Figure 6-7).
Supervised
Power Limited
151267
4.7 kΩ
UL Listed EOL
Model 7628
Figure 6-7 FACP Alarm Control Outputs
firealarmresources.com
SKE-ZN6 Six Zone Splitter Installation
Non-Supervised
Power Limited
Must be wired
within 20 feet
and in conduit.
6-9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ske-450Ske-450-zn4Ske-450-zn6

Table of Contents