Flowchart; Parameter Process Data Object Formats; Supported Parameter Process Data Object (Ppo) Type Formats - YASKAWA SI-P3 PROFIBUS-DP Technical Manual

Hide thumbs Also See for SI-P3 PROFIBUS-DP:
Table of Contents

Advertisement

Flowchart

The
Figure 7.2
illustrates the handshaking function when using a MEMOBUS/Modbus message.
*1
Toggle" means changing the HS bit status from 0 to 1 or from 1 to 0.
8

Parameter Process Data Object Formats

Supported Parameter Process Data Object (PPO) Type Formats

Set drive parameter F6-32 = 0 to use PPO type formats. The PPO is defined for cyclic data transfer, allowing the
master and the slave to exchange process data (PZD) and parameters.
The option supports five possible PPO type formats:
• PPO type 1 (8 octets PKW + 4 octets PZD)
• PPO type 2 (8 octets PKW + 12 octets PZD)
• PPO type 3 (4 octets PZD)
• PPO type 4 (12 octets PZD)
• PPO type 5 (8 octets PKW + 20 octets PZD)
All PPO Types have the registers STW, ZSW, HSW, and HIW. These registers are not mapped directly to drive
registers.
YASKAWA SIEP C730600 82E PROFIBUS-DP Technical Manual
Figure 7.2 MEMOBUS/Modbus Message Flowchart
8 Parameter Process Data Object Formats
37