Ac Input - Allen-Bradley 1606-XLE240ERL Reference Manual

Redundancy power supply - 24v, 10 a, 240 w, single-phase input
Table of Contents

Advertisement

AC Input

Attribute
AC input
AC input range
Allowed voltage L or N to earth
Input frequency
Turn-on voltage
Shut-down voltage
External input protection
AC 100V
Input current
Typ
2.63 A
Power factor
Typ
0.99
Crest factor
Typ
1.5
Startup delay
Typ
300 ms
Typ
30 ms
Rise time
Typ
75 ms
Turn-on
Max
200 mV
overshoot
Figure 1 - Input Voltage Range
P
OUT
85V
Figure 3 - Input Current versus Output Current
Input Current, typ.
6A
5
a) 100V AC
4
b) 120V AC
c) 230V AC
3
2
1
0
2
4
6
8 10 12 14 16 18
The device is suitable to be supplied from TN-, TT-, and IT mains networks
with AC voltage. For suitable DC supply voltages See
Value
Nom
AC 100...240V
Min
85...264V AC
Min
264...300V AC
Max
300V AC
Nom
50...60Hz
Typ
80V AC
Typ
72V AC
Typ
55V AC
The device is designed, tested, and approved for branch circuits up to 30 A (UL) or 32 A (IEC) without additional protection
device. If an external fuse is utilized, do not use circuit breakers smaller than 10 A B- or C-Characteristic to avoid a
nuisance tripping of the circuit breaker.
AC 120V
AC 230V
Notes
2.17 A
1.14 A
At 10 A, see
0.99
0.97
At 10 A, see
At 10 A, The crest factor is the mathematical ratio of the peak value to RMS value of the input current
1.5
1.65
waveform.
290 ms
240 ms
See
Figure
30 ms
30 ms
At 10 A constant current load, 0mF load capacitance, see
75 ms
75 ms
At 10 A constant current load, 20mF load capacitance, see
200 mV
200 mV
See
Figure
Rated
input range
max.
500ms
V
IN
264V
300V AC
a
b
c
Output Current
20 22
24A
Rockwell Automation Publication 1606-RM110A-EN-P - July 2020
Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input
Notes
Continuous operation
For maximal 500 ms (occasional)
Continuous, according to IEC 62477-1
±6%
Steady-state value, see
Steady-state value, see
Dynamic value (max 250 ms)
Figure
3.
Figure
4.
2.
2.
Figure 2 - Turn-on Behavior, definitions
Input
Voltage
Output
Voltage
Figure 4 - Power Factor versus Output Current
Power Factor, typ.
1.0
0.95
0.9
0.85
0.8
0.75
2
4
DC Input on page
Figure
1.
Figure
1.
Figure
2.
Figure
2.
- 5%
Start-up
Rise
delay
Time
a) 100V AC
b) 120V AC
c) 230V AC
Output Current
6
8 10 12 14 16 18
24A
20 22
8.
a, b
c
7