Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input
DC OK Relay Contact
12
This feature monitors the output voltage of the power supply in front of the
decoupling device.
Contact closes
As soon as the output voltage reaches Typ 22V DC.
As soon as the output voltage dips below 22V DC.
Contact opens
Short dips will be extended to a signal length of 100 ms. Dips shorter than 1 ms will be ignored.
Switching
1V
Contact ratings
Maximal 60V DC 0.3 A, 30V DC 1 A, 30V AC 0.5 A, resistive load
Minimal permissible load: 1 mA at 5V DC
Isolation voltage
See
Dielectric Strength on page 22
Figure 13 - DC OK Relay Contact Behavior
Rockwell Automation Publication 1606-RM110A-EN-P - July 2020
22V DC
<
>
1ms
1...4ms
100ms
open
closed
open
closed