Electromagnetic

Compatibility

EMC Immunity
According to the generic standards EN 61000-6-1 and EN 61000-6-2.
Electrostatic discharge
EN 61000-4-2
Electromagnetic RF field
EN 61000-4-3
Fast transients (Burst)
EN 61000-4-4
Surge voltage on input
EN 61000-4-5
Surge voltage on output
EN 61000-4-5
Surge voltage on Signals
EN 61000-4-5
Conducted disturbance
EN 61000-4-6
Mains voltage dips
EN 61000-4-11
Voltage interruptions
EN 61000-4-11
Voltage sags
SEMI F47 0706
Powerful transients
VDE 0160
(1) Criterion:
A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Device can shut-down and restart by itself. No damage or hazards for the power supply will occur.
EMC Emission
Conducted emission input lines
Conducted emission output lines
Radiated emission
Harmonic input current
Voltage fluctuations, flicker
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
(1) Restrictions apply for applications in residential, commercial and light-industrial environments, where local DC power networks according to EN 61000-6-3 are involved. No restrictions for
all kinds of industrial applications.
Switching Frequencies
PFC converter
Main converter
Auxiliary converter
The electromagnetic compatibility (EMC) behavior of the device is designed
for applications in industrial environment and in residential, commercial, and
light industry environments.
Contact discharge
Air discharge
80MHz-2.7GHz
Input lines
Output lines
DC OK signal (coupling clamp)
L N
L PE, N PE
+ -
+ / - PE
DC OK signal PE
0.15-80MHz
0% of 100V AC
40% of 100V AC
70% of 100V AC
0% of 200V AC
40% of 200V AC
70% of 200V AC
0% of 200V AC (=0V)
80% of 120V AC (96V AC)
70% of 120V AC (84V AC)
50% of 120V AC (60V AC)
Over entire load range
According to the generic standards EN 61000-6-3 and EN 61000-6-4.
EN 55011, EN 55015, EN 55022, FCC Part
15, CISPR 11, CISPR 22
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
EN 55011, EN 55022
EN 61000-3-2
EN 61000-3-3
100 kHz
80...140kHz
60 kHz
Rockwell Automation Publication 1606-RM110A-EN-P - July 2020
Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input
8 kV
Criterion A
15 kV
Criterion A
20V/m
Criterion A
4 kV
Criterion A
2 kV
Criterion A
2 kV
Criterion A
2 kV
Criterion A
4 kV
Criterion A
1 kV
Criterion A
2 kV
Criterion A
1 kV
Criterion A
20V
Criterion A
0V AC, 20 ms
Criterion A
40V AC, 200 ms
Criterion C
70V AC, 500 ms
Criterion C
0V AC, 20 ms
Criterion A
80V AC, 200 ms
Criterion A
140V AC, 500 ms
Criterion A
5000 ms
Criterion C
1000 ms
Criterion A
500 ms
Criterion A
200 ms
Criterion A
750V, 0.3 ms
Criterion A
Class B
5dB higher than average limits for DC power port
(1)
according EN 61000-6-3
Class B
Class A equipment: fulfilled
Class C equipment: fulfilled in the load range from 8 to
24 A
Fulfilled, tested with constant current loads, non-
pulsing
Fixed frequency
Output load dependent
Fixed frequency
(1)
19