Input Inrush Current

An active inrush limitation circuit limits the input inrush current after turn-on
of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first
microseconds after switch-on.
Attribute
Max
Inrush current
Typ
Typ
Inrush energy
Max
Figure 6 - Typical Turn-on Behavior at Nominal Load, 120V AC Input, and 25 °C (77 °F) Ambient
Figure 7 - Typical Turn-on Behavior at Nominal Load, 230V AC Input and 25 °C (77 °F) Ambient
Rockwell Automation Publication 1606-RM110A-EN-P - July 2020
Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input
AC 100V
AC 120V
AC 230V
11 A peak
7 A peak
11 A peak
9 A peak
6 A peak
6 A peak
9 A peak
6 A peak
9 A peak
2
2
0.1 A
s
0.1 A
s
0.4 A
50ms/DIV
Input current
2A/DIV
6A
Input voltage
250V/DIV
Output voltage 20V/DIV
50ms/DIV
6A
Input current
2A/DIV
Input voltage
500V/DIV
Output voltage 20V/DIV
Temperature
At 40 °C (104 °F), cold start
At 25 °C (77 °F), cold start
At 40 °C (104 °F), cold start
At 40 °C (104 °F), cold start
2
s
9