Charging of Batteries

This redundancy power supply is ideal for charging batteries due to the
decoupling circuit built in to the output stage which does not require a fuse or
diode between the power supply and the battery.
It can be used to charge sealed lead acid (SLA) or valve regulated lead acid
(VRLA) lead batteries when following these instructions:
Set output voltage (measured at disconnected battery) very precisely to the
end-of-charge voltage. Use the potentiometer, which is hidden behind the flap
on the front of the unit. See See
Battery Temperature 10°C (50 °F)
End-of-charge
27.8V
Ensure that the ambient temperature of the power supply stays below
40 °C (104 °F).
Use only matched batteries when connecting 12V types in series.
The return current to the power supply (battery discharge current) is
typically 11mA when the power supply is switched off.
Rockwell Automation Publication 1606-RM110A-EN-P - July 2020
Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input